The operating principle of the Aqua-Mat- Q outflow control is based on the setting of a defined outflow cross-section by means of a control slide valve depending on the measured throttle outflow.
If the flow increases, the slide valve is closed further. If the flow drops, the slide valve is opened further. In this way, the desired throttle discharge can be kept constant via a simple control loop.
Furthermore, the Aqua-Mat- Q control is programmed in such a way that an upper water level that can be preset as a setpoint is not exceeded. If the corresponding setpoint is reached, the control switches from flow control mode to backwater target maintenance mode.
In suction target mode, enough water is always transferred to the treatment plant so that the water level limit is not exceeded. For this function, an additional US probe is required to record the headwater level.
The accuracy of the Aqua-Mat- Q discharge control is independent of the knowledge of the discharge coefficient of the control valve used, since here it is not controlled via the disturbance variable, but via the result. Therefore, this regulation is one of the most precise of its kind.
| Reference 1: | Reference 2: | Reference 3: | |||
| Project name: | Olsberg | Project name: | Olsberg | Project name: | Olsberg |
| Project data: | Year of construction 2021 DN = 200 Q = 31 l/s Number 1 piece | Project data: | Year of construction 2021 DN = 400 Q = 183 l/s Number 1 piece | Project data: | Year of construction 2020 DN = 250 Q = 56 l/s Number 1 piece |
| Scope of services: | Manufacture, delivery and assembly | Scope of services: | Manufacture, delivery and assembly | Scope of services: | Manufacture, delivery and assembly |
Specification Text AquaMat Q
Sample specification for planners and specifiers. Ready to be adopted into your bill of quantities.
AquaMat Q – Flow Regulator
Proof of delivery:
SGS Aqua Technologies GmbH
Burmeckestraße 4–6, D-59955 Winterberg
Tel.: +49 2983 974268-0
Fax: +49 2983 974268-68
Consisting of
- Measurement and control system with the following devices:
Penstock DN ______ as integrated flange design, incl. hand wheel
Flow meter as partial fill design
Electrical drive penstock DN ______ as integrated flange design, incl. penstock and electric drive
Tube coupler for length and elbow variations DN ______ - Tube parts of the measurement and control system:
2 F-parts with wall collar DN ______, length: ______ mm
2 F-parts DN ______, length 1: ______ mm / length 2: ______ mm
1 FF-part DN ______, length: ______ mm - Bypass with the following parts:
Penstock DN ______ as integrated flange design, incl. hand wheel - Tube parts of the bypass:
2 F-parts with wall collar DN ______, length: ______ mm
1 F-part DN ______, length: ______ mm - For the installation of the wall tubes during the civil work, a spacer with two flanges on each side is to be delivered. This guarantees a better and dimensionally accurate installation. After the spacer has been removed and the piping of the system has been installed, the spacer remains with the contractor.
Control cabinet
- Outdoor cabinet incl. socket, complete electrical installation incl. main switch, fuses, lights, heating system and system-necessary components
- Control system with PLC and AquaMat Q software component
- Documentation and assembly instruction
Required functions
- Characteristic curve and flow regulation for ______ l/s, based on client standards
- Trouble report as floating relay contacts
- Penstocks must be operable from outside the shaft
- Optional clogging control
- Optional telecontrol unit
Item
| Pos. | Description | Quantity / Unit | Unit price | Total price |
|---|---|---|---|---|
| 01. | AquaMat Q flow regulator – supply and installation | 1,000 pc | ____________ | ____________ |
Sample specification text SGS Aqua Technologies GmbH · Version 02.01.2023 · All information without guarantee.